FIRE BREAK DAMPER

 

The electric-mechanically activated Fire Break Damper, is especially built for application in Kitchen exhaust ducts located in places indicated by specific technical standards and adequate for use in exhaust systems with high levels of fat. In this manner, it must be fully built in black plates with a minimum gauge equivalent to or above that of the ducts, should not have activation elements, or internal obstacles which may be incrusted with fat, jeopardizing its operation, be entirely water, smoke or flame proof, resistant to fires for at least 1 hour, have a manufacturer's identification label, be structured as a spool and have connections on both sides with flanges equipped with fire resistant joints for the coupling to the ducts and allowing easy removal for internal cleaning; it should not have any kind of lateral openings which may reduce its resistance to internal explosions and must be externally painted with a protective anti-oxidizing finish.

The Fire Break Damper must also comply with the ABNT Technical Standard no. 14.518 which also covers fire prevention in Kitchens and the like.

   

 

 

 

 